Effect of electronic anti-fouling treatment on fouling mitigation with circulating cooling-tower water
Journal article   Peer reviewed

Effect of electronic anti-fouling treatment on fouling mitigation with circulating cooling-tower water

Won Tae Kim, Young I. Cho and Cheolho Bai
International communications in heat and mass transfer, v 28(5), pp 671-680
2001

Abstract

The purpose of the present study was to investigate the effect of electronic anti-fouling (EAF) technology on fouling mitigation in a heat exchanger in an open cooling-tower system. Two tests were performed in a rectangular heat-transfer channel at 5 cycles of concentration: one without the EAF treatment and the other with the EAF treatment. The fouling resistance in the case with the EAF treatment was about 70% less than that in the case without the EAF treatment at the end of 270-hr tests.