Abstract
Disinfection processes have often been characterized by the “CT” concept i.e., the product of disinfectant residual and contact time (perhaps as a function of pH, temperature, and other water quality variations) produces a given level of disinfection. The objective of this work was to develop and validate the use of reaction kinetic models for disinfection process design. Using bench scale (batch) kinetic information, and hydraulic characterization of pilot scale continuous disinfection processes, predictions of continuous process performance were made using a segregated flow model. These predictions were compared to independent experimental measurements of actual inactivation in pilot scale processes. Preammoniation, free residual chlorination, and ozonation were used on two waters from Portland, Oregon (US). Organisms used were Giardia muris, bacteriophage MS2, and Escherichia coli.
Metrics
15 Record Views
Details
- Title
- Predicting disinfection performance in continuous flow systems from batch disinfection kinetics
- Creators
- Charles Haas - Drexel UniversityJosh Joffe - Malcolm Pirnie, Inc., One International Boulevard, Mahwah, NJ 07495-0018, USAMark Heath - 2415 NE 42nd St., Portland. OR 97213, USAJoseph Jacangelo - Montgomery Watson Engineers, 560 Herndon Parkway Suite 300, Herndon, VA 22070-5240, USAUma Anmangandla - PRC Environmental Management Inc., 1800 JFK Boulevard, 6th Floor, Philadelphia, PA 19103, USA
- Publication Details
- Water science and technology, v 38(6)
- Publisher
- IWA Publishing
- Resource Type
- Journal article
- Language
- English
- Academic Unit
- Civil, Architectural, and Environmental Engineering
- Other Identifier
- 991019168996004721